Medium Voltage Current Transformers
Salient Features :
- Oil impregnated paper insulation
- Accuracy class, output & number of secondary windings as desired
- Graded insulation for primary
- Hermetically sealed
- Technical Parameters


Technical Parameters :
Description |
12 kV |
36 kV |
1 min. power frequency voltage
Lighting impulse voltage
Rated frequency
Short time thermal current for 3 sec
Dynamic withstand current
Total creepage distance
Primary account |
28 kV rms
75 kV peak
50 Hz
25 kA rms
62.5 kA peak
300 mm
Up to 1250-higher currents can be supplied on demand |
70 kV rms
170 kV peak
50 Hz
25 kA rms
62.5 kA peak
900 mm
Up to 1600-higher currents can be supplied on demand |
|