Product Range Switchgear Products Division

EHV Gas Insulated Switchgear

Salient Features :

  • Only very small space is required as compared to conventional air insulated switchgear
  • Modular construction
  • Minimum maintenance
  • Plug- in type cable terminations
  • Hermetically sealed enclosures
  • Mechanism is of M2 class
  • Hydro spring operating mechanism for circuit breaker
  • Each section of SF6 gas is compartmentalized with insulating barrier between enclosures and sealed with O-Rings
  • No environmental influences
  • Electrical interlocking systems are equipped for the purpose of protecting the operator and safe operation of main circuit
  • Gas section of circuit breaker is provided with dual alarm systems
  • Gas monitoring is available from the control board easily
  • Compatible to remote operation
  • Full safety to operator

Technical Parameters :

Description

245 kV GIS

420 kV GIS

Rated voltage
1 min. power frequency withstand voltage
Rated lighting impulse withstand voltage
Rated switching impulse withstand voltage
Rated current
        - Busbar
        - Line
Rated current frequency
Circuit Breaker
Rated short circuit breaking current
Rated short circuit breaking current
Break time (max)
Type of drive
Opening time
Closing time (max)
First pole to clear factor
Current transformer

245 kV rms
460 kV rms


1050 kV peak


Not Applicable




3150 A
Up to 2500
50 Hz
50 kA rms
125 kA peak
40 ms
Hydraulic-Spring
30 ms
100 ms
1.3
As per customer requirement

420 kV rms
520 kV rms


1425 kV peak


1050 kV peak




4000 A
Up to 3150
50 Hz
50 kA rms
125 kA peak
40 ms
Hydraulic-Spring
30 ms
100 ms
1.3
As per customer requirement

 